Trouble
|
Possible causes
|
Solutions
|
Motor
only runs in one direction.
|
The
wire connector terminal block becomes loose.
|
Check
wire connector terminal block make sure it is plugged in
terminal block 10.
|
The
limit switch wire connector terminal block becomes loose.
|
Check
limit switch wire connector terminal block make sure it is
plugged in terminal block 9.
Check
the limit switch mode.
|
The
electric component on the control board such as Q2, Q91 or
Q92 may be damaged.
|
Replace
the electric component Q2, Q91 or Q92 (BTA16/600) or
replace the board.
|
By
pressing button 1(button 2 or button 3) which has been
programmed to open the gate, press the same button again
to stop the gate in required position, but the gate will
auto-close immediately.
|
The
auto-close time is too short.
|
Reset
the auto-close time. See Set auto-close function
section.
|
When
you use button 4 of remote control to open the gate, gate
travels too short.
|
The
width of pedestrian mode is too narrow.
|
Reset
the width of pedestrian mode. See Set width of
pedestrian mode section.
|
When
you use button 4 of remote control to open the gate, but
the gate will auto-close immediately.
|
The
auto-close time of pedestrian mode is too short.
|
Reset
the auto-close time of pedestrian. See Set auto-close
function of pedestrian mode section.
|
The
gate will not open or close.
|
The
limit switch wire connector terminal block becomes loose.
|
Check
the limit switch mode (see table 1 Dip-switch).
|
Connecting
wires or terminal blocks are too loose.
|
Check
the connecting wires and terminal blocks.
|
The
electric component on the control board such as Q2, Q91 or
Q92 may be damaged.
|
Replace
the electric component Q2, Q91 or Q92 (BTA16/600) or
replace the board.
|
Power
switch is OFF
|
Make
sure power switch is ON.
|
Remote
control does not work
|
The
indicator light of remote control does not light.
|
Check
the batteries on your remote control
|
Remote
control is not suitable for receiver.
|
After
making sure the codes are correct, erase remote controls
and then re-program the codes in the device. See Adding
extra remote controls (learning) section.
|
Broken
receive board
|
Replace
receive board.
|
When
you open the gate by using button 1(button 2 or button 3)
which has been programmed, gate will stop in mid-travel or
reverse before reaching the fully limit position.
|
The
Force Adj. (VR1) is adjusted too small.
|
Check
the Force Adj.
(VR1). Adjust VR1 to increase force.
|
Gate
is obstructed.
|
Remove
the obstruction.
|
The
remote control operating distance is too short.
|
Signals
are shielded by the gate.
|
Link
a new antenna (1~1.2m BVR 0.75mm2) to the old
antenna. Then fix the antenna on the wall vertically, make
sure the total height from the top of antenna to the
ground is approx. 1.5m.
|
The
gate opener is opening in the wrong direction. (Gate is
opening to the right when you are inside the property and
facing the gate)
|
This Sliding Gate Operator is wired to be mounted
as right hand installation.
|
If
your gate requires left hand operation:
Reverse
MOTOR WIRES
V and W
at terminal
block 20
And,
Reverse
LIMIT SWITCH WIRES CL and OP at terminal block
9.
|
GATE DOES NOT STOP WHEN IT REACHES OPEN OR CLOSE
POSITION
|
Limit Switches or wiring improperly installed or
damaged.
|
1) Check the position of the magnets.
2) Check the wires to limit switch block 9.
|